Rheem Heat Pump Auxiliary Heat On Constantly: Fixes

Last updated Oct 9, 2026 · By fixme.vip Editorial

Rheem Heat Pump: Auxiliary heat on constantly
Applies to: Rheem and Ruud split heat pumps with electric heat kits or air handlers, including Classic, Classic Plus and Prestige series. Behavior varies by thermostat: conventional 24V thermostats call aux on the W2 terminal, while EcoNet-communicating systems use their own staging logic and lockout settings. Defrost control boards also vary by series.
Typical repair cost: $0 for thermostat settings – $1,500+ if a refrigerant leak must be found and repaired — compare free local quotes

Get this fixed by a local pro

Free, no-obligation quotes from licensed HVAC technicians in your area. Compare up to 3 estimates before anyone visits.

Get free local quotes

Rheem heat pump auxiliary heat on constantly: what it means

“Auxiliary heat on constantly” is not a numbered fault code on Rheem heat pumps. It’s a symptom. The thermostat shows “Aux Heat” (or “Aux”) nearly all the time, or the electric bill jumps while the house still feels warm. On a Rheem or Ruud split system, the electric heat strips in the air handler are being called for, or energized, far more than they should be.

Aux heat comes on for one of three reasons:

There is nothing to reset. The condition stays until the cause is corrected. A flashing light on the outdoor board is a separate diagnostic and is covered on its own page.

Aux heat that runs in genuinely cold weather can be normal. The outdoor temperature where this starts, often roughly 25–35°F, is called the balance point. It depends on how fast your home loses heat compared with how much heat your heat pump can deliver. The concern is aux running constantly in mild weather.

Rheem heat pump auxiliary heat on constantly: common causes, ranked by probability

  1. Thermostat set to Emergency Heat, or set up incorrectly. This is especially common after a new thermostat install. Any of these can cause it:

    • The thermostat is left on EM Heat.
    • It is configured as “conventional/furnace” instead of “heat pump.”
    • The O/B reversing valve setting is wrong. Rheem uses O, energized in cooling.
    • Aux lockout or droop settings are too aggressive.
  2. Large setbacks or temperature jumps. Raising the setpoint several degrees triggers aux recovery heat on most thermostats.

  3. Heat pump not producing enough heat. Common reasons:

    • Low refrigerant charge from a leak
    • A failing compressor or capacitor
    • An outdoor fan problem
    • A restricted coil

    The compressor runs, but the thermostat can’t reach setpoint, so it adds aux.

  4. Restricted airflow. A dirty filter, closed registers or a dirty indoor coil can cause this. Low indoor airflow reduces the heat delivered to the rooms. Heating calls then run longer, and the thermostat is more likely to bring on aux.

  5. Outdoor unit stuck in or frequently entering defrost. Aux normally runs during defrost. Excessive defrost cycles or a faulty defrost board mean excessive aux time.

  6. Stuck heat strip relay or sequencer in the air handler. The strips stay energized even with no W2 call. Signs include warm air with the blower off, or heat when the thermostat is off.

  7. Wiring fault. A shorted or miswired W2/E conductor sends a constant aux call.

  8. Outdoor thermostat or balance point setting (where installed). A misadjusted outdoor thermostat or EcoNet lockout temperature can allow strips in mild weather.

How to fix Rheem heat pump auxiliary heat on constantly: safe checks first

How a technician will diagnose it

Symptom, cause and what to do

SymptomLikely causeDIY actionTechnician job
”Em Heat” shown on thermostatEmergency heat mode left onSwitch mode to HeatNone needed unless the outdoor unit isn’t running
Aux after every morning warm-upLarge setback recoveryUse 2–3° setbacks; enable smart recoveryAdjust staging or lockout if requested
Aux constant after new thermostatWrong system type or O/B settingCheck installer settings per manualCorrect wiring and configuration
Outdoor unit not running, house still warm-ishTripped outdoor breaker, failed capacitor or contactorReset breaker onceTest and replace the capacitor or contactor
Unit runs but air is lukewarm, aux kicks inLow refrigerant or weak compressorReplace filter, open registersLeak search, repair, recharge; compressor tests
Frequent defrost with auxDefrost board or sensor faultClear snow and debris from around the unitTest and replace the defrost board or sensor
Heat with the thermostat off, or burning smellStuck heat strip relay or sequencerSmoke, strong burning odor or scorching: leave the home and call 911. Otherwise, switch off the air handler/heat strip breaker or disconnect (not just the thermostat). Then call promptly.Replace the relay, sequencer or control
Constant aux call in all modesShorted W2 wiringNoneTrace and repair the wiring

Rheem heat pump auxiliary heat on constantly repair cost

Typical US ranges, including parts and labor:

RepairTypical cost
Thermostat setting correction$0 DIY; $100–$200 service call
New heat-pump-compatible thermostat$50–$250 DIY; $150–$450 installed
Air filter$5–$40
Capacitor replacement$150–$400
Contactor replacement$150–$350
Heat strip relay or sequencer replacement$150–$450
Defrost sensor$150–$350
Defrost control board$300–$700
Wiring repair$150–$400
Refrigerant leak search plus recharge$400–$1,500+
Coil replacement$1,500–$3,000+
Compressor replacement$1,800–$4,000+

Warranty coverage on Rheem parts may reduce parts cost if the unit is registered. Registration deadlines and labor exclusions vary by product line, so check your warranty terms before assuming parts are covered. Labor is usually extra.

Safety first: anything beyond filters, batteries, and visual checks on gas-burning equipment should be handled by a licensed technician. Repeatedly resetting a locked-out unit can mask a dangerous fault. When in doubt, get a pro.

Parts & tools for this fix

As an Amazon Associate, fixme.vip earns from qualifying purchases. Prices and availability are on Amazon.

Frequently asked questions

Is it normal for aux heat to come on with a Rheem heat pump?

Yes, sometimes. Aux heat normally runs during defrost cycles, during large temperature jumps such as recovering from a setback, and in very cold weather when the heat pump can't keep up alone. It is not normal for aux to stay on all the time in mild weather.

What is the difference between aux heat and emergency heat?

Aux heat runs electric strips alongside the heat pump compressor. Emergency heat shuts the compressor off and heats with the strips only. If the thermostat is left on emergency heat, the strips run every time there is a call for heat, and that alone can explain a very high bill.

Can running aux heat constantly damage my system?

It usually won't damage anything right away, but it is expensive. Electric strips can cost two to three times as much to run as the heat pump. If a strip relay is stuck closed, the strips may also heat with the blower off, which is a safety and overheating concern. That needs a technician promptly.

Will lowering my thermostat setting fix it?

Big setbacks often make it worse. When you raise the temperature several degrees in the morning, many thermostats bring on aux heat to recover. Smaller setbacks of 2 to 3 degrees, or a thermostat with smart recovery, usually reduce aux run time.

Different code on your heat pump? Look it up — and if we haven't covered it yet, telling us is how it gets written next.